Click to enlarge image
|
- Sure operating using latch mechanism.
- Large current capacity with small operating current.
- Good performance, closing capacity-12 times as large
as rated current.
- Compact and light weight.
- SuitabIe for emergency power supply facilities.
- Switchable between AC and DC
|
| |
|
TYPE |
606T, 61T
606TB, 61TB |
62T
62TB |
64T
64TB |
|
RATED CURRENT |
AC600V
/ DC125V |
|
RATED CURRENT(le) |
60 100A |
200A |
400A |
|
KIND OF THROW |
DOUBLE
THROW |
|
CUNNECTION |
FRONT,
BACK |
|
NUMBER OF POLES |
2P |
3P |
4P |
2P |
3P |
4P |
2P |
3P |
4P |
|
WEIGHT(Kg) |
14 |
16 |
18 |
16 |
19 |
21 |
16 |
19 |
21 |
|
OPERATING
CURRENT |
DC 110V |
14A |
14A |
14A |
14A |
14A |
14A |
14A |
14A |
14A |
|
AC 100V / 110V |
14A |
14A |
14A |
14A |
14A |
14A |
14A |
14A |
14A |
|
AC200V / 220V |
7A |
7A |
7A |
7A |
7A |
7A |
7A |
7A |
7A |
|
PERFORMANCE |
RATED SHORT-TIME CURRENT (1SEC) |
5kA |
10kA |
12kA |
|
PEAK SHORT-TIME CIRCUIT PEAK VALUE |
12.5kA |
25kA |
30kA |
|
SWITCHING CAPACITY |
10le MAKING
/ 8le BREAKING cos ?nbsp;=0.35
le MAKING / le BREAKING L/R=1ms |
|
LIFE |
ELECTRICAL
1.000TIMES MECHANICAL 5.000TIMES |
|
SWITCHING FREQUENCY |
6 TIME/HOUR |
|
|
|
|
|
| |
|
|
|